Seal the path
Blanking panels, side seals, brush strips, and door fit matter when cabinet loads rise.
Estimate the airflow needed to remove IT cabinet heat, then compare it with available fan or room airflow. The calculator converts cabinet watts to BTU/hr, CFM, m3/h, cooling tons, inlet temperature, exhaust temperature, containment leakage allowance, and planning headroom.
Use metered rack PDU load when possible. Nameplate power often overstates actual heat, while hidden support loads can understate room cooling demand.
CFM estimates assume sensible air cooling at standard conditions. They do not model humidity, fan pressure, liquid cooling, or CFD airflow paths.
Enter cabinet heat load and airflow details to calculate CFM, temperature rise, and headroom.
| Metric | Value | Notes |
|---|---|---|
| No calculation yet. | ||
The calculator treats electrical power used inside the cooled cabinet zone as sensible heat. The airflow model uses the standard sensible-air HVAC relationship for early planning. Real cabinets also depend on static pressure, fan curves, cable blockage, blanking panels, containment leakage, bypass air, and return-air path.
Heat load
installed watts = cabinet count x average cabinet watts or the entered total IT load
design watts = (installed watts + support heat) x (1 + growth%) x (1 + margin%)
Unit conversions
BTU/hr = watts x 3.412141633
tons = BTU/hr / 12000
m3/h = CFM x 1.6990108
Sensible airflow
thermal CFM = BTU/hr / (1.08 x temperature rise F)
containment CFM = thermal CFM x (1 + leakage%)
rated airflow needed = containment CFM / usable airflow%
Temperature estimate
estimated inlet = supply air + recirculation gain
estimated exhaust = estimated inlet + target temperature rise
Airflow capacity is not the same as cooling success. A cabinet can show enough total CFM and still overheat if cold air bypasses the equipment, hot exhaust recirculates to the front, filters are loaded, doors restrict flow, cable bundles block intakes, or fans cannot overcome static pressure.
Use this as a screening tool before a production review. High-density cabinets should be checked against manufacturer inlet-temperature limits, room cooling redundancy, breaker and PDU capacity, UPS runtime, rack weight, floor loading, fire protection, containment design, and measured operating data.
Cabinet CFM is the airflow needed through or to a cabinet to carry heat away while keeping equipment inlet temperatures within the planned limit.
A larger allowed air temperature rise lets each cubic foot of air carry more heat, so calculated CFM falls. The tradeoff is a warmer exhaust stream and less margin for recirculation.
Usually no. Leakage is an airflow delivery allowance, not extra electrical heat. This calculator increases required delivered airflow for leakage while keeping heat load separate.
Enter cooling capacity in tons to check whether total cooling capacity is large enough. You still need airflow and containment checks because tons alone do not prove air reaches the cabinet intakes.
Yes. Choose deg C and enter temperatures and temperature rise in Celsius. The calculator converts the rise internally for the CFM equation.
Yes. All calculations, copy actions, and CSV export happen in your browser.
Blanking panels, side seals, brush strips, and door fit matter when cabinet loads rise.
Front-of-cabinet inlet temperature tells you more than room average temperature.
Nameplate fan CFM can be optimistic once filters, grilles, doors, and cable bundles add pressure.
Maintenance states, dirty filters, hot days, and growth can consume narrow airflow headroom quickly.